calorimetric flow meter / for compressed air / insertion / programmable
SD0523
Vnation JSC
-
Technology:
calorimetric
-
Fluid:
for compressed air
-
Mounting:
insertion
-
Other characteristics:
programmable
-
Process pressure:
16 bar (232.06 psi)
-
Process temperature:
Min.: 0 ?C (32 ?F)
Max.: 60 ?C (140 ?F)
-
Volumetric flow rate:
Min.: 548 m?/h (19352.44 ft?/h)
Max.: 29560 m?/h (1043901.53 ft?/h)
For inside pipe diameters of 38 mm to 254 mm
Can be used for consumption measurement and leakage monitoring
Final value of the measuring range from 548 Nm3/h to 29,560 Nm3/h
Exact flow rate and temperature measurement of compressed air
Binary, analogue and pulse outputs
Flow rate measurement in standard cubic metres
Calorimetric measuring principle
Measuring, display and setting ranges of the compressed air meter refer to the standard volume flow according to DIN ISO 2533. This makes a correction using the temperature and the pressure unnecessary. The fast response time and the high response sensitivity of the system also allow the reliable detection of small volumetric flow quantities.
Adaptation to variable pipe sizes
The measuring ranges for different pipe sizes are stored as reference values in the sensor and can be called and set via the programming buttons.