three-phase switchgear / AC / metal-clad / power distribution
KYN28A-12
Vnation JSC

-
Electrical characteristics:
three-phase, AC
-
Configuration:
metal-clad
-
Applications:
power distribution, power plant
-
Current:
Min.: 630 A
Max.: 3150 A
-
VAC:
Min.: 13.8 kV
Max.: 20 kV
Parameters:
Rated Voltage (Highest Service Voltage: 12kV
1min Power Frequency Withstand Voltage: 42kV
Lightning Impulse Withstand Voltage: 75kV
Rated Frequency: 50Hz Protection Level: Enclosure IP4X
Applicable standard: IEC298, GB3906
Description:
KYN28A-12 Indoor Metal-clad Mid-mounted Switchgear, a indoor complete equipment, which is available to single busbar or double busbar power net for power transmission, distribution, and mainly used as measuring, protecting and controlling in power transmission and distribution system.
Application:
-Power supply of plant, medium or small generator, distribution of factory and mining
-Power acceptance and transmission from the secondary substation in the power system
-Starting of large HV electromotor
Features:
-Attractive appearance, convenient installation and maintenance
-Better in mechanical strength, high accuracy
-Ensure personnel security