draw-wire position sensor / mechanical / ISS
SGU100 series
Vnation JSC

-
Type:
draw-wire
-
Technology:
mechanical
-
Output signal:
ISS
-
Measuring range:
Min.: 200 mm
Max.: 1600 mm
How energy efficiency is improved
Enables the demand-led, energy-efficient and safe air-volume control of laboratory fume cupboards in combina-tion with the ASV115CF152 compact controller for critical areas.
Areas of application
Infinitely-variable measurement of the position of the vertical sash in fume cupboards.
Features
Non-wearing and accurate detection of the position of the sash with a travel resolution of < 1 mm (F010) or < 2 mm (F011)
Enables fast and oscillation-free volume flow control
Easy to fit, preferably on the counterweight of the sash
Teach-in function for adjusting travel of the sash
RS-485 bus interface for up to 31 subscribers in a segment and SLC (Sauter Local Communication) protocol
Extremely easy to parameterise using the SAUTER CASE VAV software
Integrated excess-travel alarm
Power cable 2.5 m long, 7 x 0.32 mm?, fixed to housing
Fitted with halogen-free cable as standard
Remote access and remote maintenance: commissioning and service via bus or external button
Service support for the entire system through a voltage controller function in test mode
3-colour LED status display
Acoustic status and alarm elements (can be deactivated)